WWW.BALTIMOREAIRCOIL.COM
9
Unit Rigging & Assembly
Multi-Cell Installation
Optional Positive Closure Plate
Fan Guard Installation
One-Piece Fan Guard
Fan Guard Installation
Due to height limitations on truck shipments, the fan guard may ship unmounted. Never
step or walk on the fan guard when installed. Refer to Table 2 for the number of fan guard
pieces Series 3000 Cooling Towers will have .
DANGER: Fan guard must be
securely in place before the cooling
tower is placed in operation. Never
step or walk on the fan guard.
Failure to follow these instructions
may result in serious injury or
death.
NOTE:
1. Existing 3/8” stud and nut for
guard mounting at fan deck
level (3/8” x 1 1/2” bolt for
guards mounted on top of cowl
extensions).
Figure 13. One-Piece Fan Guard Assembly
See Detail A
Detail A
Fan Guard Clip
3/8" Locknut
Fan Guard
Model Number
Number of Fan
Guard Pieces
S3E/XES3E-8518-xxx 1
S3E/XES3E-1020-xxx, 1222-xxx, 1424-07x 2
S3E/XES3E-1424-12x, 1424-13x, 1424-14x 4
Table 2. Number of Fan Guard Pieces
One-Piece Fan Guard
Mount fan guard to unit as illustrated in Figure 13, Detail A.