4 Technical data
4.5. PROFINET
PROFINET port
1 x 10Base-/100Base-Tx
Connection for PROFINET port
M12, D-coded
Cable types per IEEE 802.3
Shielded twisted pair min. STP CAT 5/ STP CAT 5e
Data transmission rate
10/100 Mbit/s
Max. cable length
100 m
Flow control
Half Duplex/Full Duplex (IEEE 802.33x-Pause)
4.6. Function
indicators
Module status
LED
Status
Function
US
green
Input power OK
red
Low Input power (<18V)
UA
green
Output power OK
red
Low Output power (< 18V)
SF
off
No error
red
Watchdog timeout; channel, generic or extended
diagnosis present; system error
red flashing
DCP signal service is initiated via the bus
BF
off
No error
red
No configuration; or low speed physical link; or no
physical link
red flashing
No data exchange
100
off
Bus clock: 10 Mbit/s
yellow
Bus clock: 100 Mbit/s
LK
green
Data transfer
I/O Port
Each port has two two-colour LEDs to indicate the I/O-States
Status
Function
Description
off
I/O State
State of the Input or Output Pin is 0
yellow
I/O State
State of the Input or Output Pin is 1
Status
Port configuration
Diagnostic Input
Input
Output
red
Input low
short-circuit between
Pin 1 und 3
short-circuit on output
Pin
red
flashing
_
_
short-circuit between
Pin 1 und 3
Status LEDs
Port LEDs