EasyManua.ls Logo

Balluff BNI PNT-104-105-Z015 - Channel Number; Channel Properties; Type; Accumulative

Balluff BNI PNT-104-105-Z015
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Balluff Network Interface Profinet
www.balluff.com
21
6 Diagnostics
6.4. Channel Number
Configuration as standard I/O
Error Type
Channel Number
Undervoltage US
8000
Undervoltage UA
8000
No UA
8000
Sensor Short circuit Pin 1 - 3
0…..n
Actor Short circuit Pin 2 - 3
0…..n
Actor Short circuit Pin 4 - 3
0…..n
6.5. Channel
Properties
2 bytes, subdivided as follows:
Type
Bit 0-7
Possible
values
Meaning
0x00
Used if the channel number is 0x8000 or none of the types defined
below is relevant.
0x01
1 bit
0x02
2 bits
0x03
4 bits
0x04
8 bits
0x05
16 bits
0x06
32 bits
0x07
64 bits
0x08 0xFF
Reserved
Accumulative
Bit 8 not used, always 0.
Maintenance
Bit 9-10
Possible values
Meaning
Bit 9
Bit 10
0x00
0x00
Diagnostics

Table of Contents