22
6 Diagnostics
Specifier
Bit 11-12
Possible
values
Meaning
0x00
Not used
0x01
Diagnosis appeared
0x02
Diagnosis left
0x03
Diagnosis left, but another is still active
Direction
Bit 13-15
Possible
values
Meaning
0x00
Manufacturer-specific
0x01
Channel used as input
0x02
Channel used as output
0x03
Channel used as input and output
6.6. Channel Error
Type
Error code in hex
Description
0x0000
Unknown error
0x0001
Short-circuit
0x0002
Undervoltage
0x0003
Overvoltage
0x0004
Overload
0x0005
Temperature limit exceeded
0x0006
Cable break
0x0007
Upper threshold exceeded
0x0008
Lower threshold undershot
0x0009
Error
0x001A
External error
0x001B
Sensor has incorrect configuration (IO-Link device)
0x0101
Actuator warning
0x0105
Actuator supply undervoltage
0x0104
No actuator power supply