3 Getting Started
3.2. Mechanical
connection
The module is attached using 2 M6 screws and 2 washers.
Isolation pad as accessory available
3.3. Electrical
connection
Power Supply
Power supply “IN” (7/8”, male)
Pin
Function
Description
1
GND Bus- / Sensor and actuator
power supply
0 V
2
3
Function ground
FE
4
Bus- / Sensor power supply
+24 V
5
Actuator power supply
+24 V
Power supply OUT (7/8” female)
Pin
Function
Description
1
GND Bus- / Sensor and actuator
power supply
0 V
2
3
Function ground
FE
4
Bus- / Sensor power supply
+24 V
5
Actuator power supply
+24 V
Note
Provide sensor/bus power and actuator power from separate power sources if
possible.
Total current <9A per Pin. The total current of all modules may not exceed 9A
even when daisy chaining the actuator supply.
Grounding
Note
The FE connection from the housing to the machine must be low-impedance
and kept as short as possible.
PROFINET
Interface
M12, D-coded, female
Pin
Function
1
Tx+
Transmit Data +
2
Rx+
Receive Data +
3
Tx-
Transmit Data -
4
Rx-
Receive Data -
Note
Unused I/O port socket must be fitted with cover caps to ensure IP67 protection
rating.

Table of Contents