Q4X BASICS
1. For black/dark targets and highly reflective targets, set the “SPd” to 50ms
2. If using a reflective target, put a 5-15° tilt on the sensor to avoid specular reflection
3. Always try and make sure the green “STB” light is solid on the display of the sensor
4. Locking and Unlocking The Sensor - Press and hold the “+” button and tap the -“ button four times. This can
both lock and unlock the Q4X sensor and the display with flash the condition (“Loc” or uLoc”).
Q4X Factory Default Reset
1. Press and hold the MODE/- button for more than 2 seconds until “tch” shows up on the display.
2. Press the MODE/- button once. The display will read “rSEt” for Reset.
3. Press Select/TEACH button to enter the Reset submenu.
4. The display should read “no”. Press the “-“ button once. The display will read “yes”.
5. Press the SELECT/TEACH button to reset the sensor to factory defaults and return to Run mode.
Q4X Adjust Switch Point/ Window Size
1. In run mode click + or button (momentary). Current switch point will display (flashing slowly)
2. Use + and buttons to in adjust position.
3. Click SELECT/TEACH to confirm the adjusted switch point
Q4X Active TEACH Indicators (DYN, FGS, and BGS)
1. Two-point TEACH mode selected (default) DYN, FGS, and BGS all off
2. Dynamic TEACH mode selected DYN on
3. Foreground suppression TEACH mode selected FGS on
4. Background suppression TEACH mode selected BGS on
5. Dual TEACH mode selected DYN, FGS, and BGS all on

Other manuals for Banner Q4X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Banner Q4X and is the answer not in the manual?

Banner Q4X Specifications

General IconGeneral
Sensing ModeDiffuse
Input Voltage10 V DC to 30 V DC
OutputNPN or PNP
Housing MaterialStainless steel
IP RatingIP67
Connection TypeM12