DGC-2020ES BESTlogic™Plus
Name
Description
Symbol
Status Input
Pre Start Input
True when the DGC-2020ES is indicating that the
Pre Start relay should be closed.
Status Input
Regen
Completed
True for 30 seconds after a Yanmar ECU goes back
into passive mode when the status of the DPF
Active Regeneration Forced Status is “Regen
Successful”.
Status Input
Regen
Confirmation
Requested
True after a manual exhaust regeneration has been
requested on a Yanmar ECU. Once in this state,
another regen request must be issued to confirm
manual regeneration.
Status Input
Regen Interlock
from ECU
True when John Deere proprietary parameters are
broadcast over the J1939 CAN Bus.
Status Input
Regen Stopped
True for 30 seconds after a Yanmar ECU goes back
into passive mode when the status of the DPF
Active Regeneration Forced Status is “Regen Not
Successful”.
Status Input
Reset Active
True when the Reset logic element is true or when
the Reset key on the front panel is pressed.
Status Input
Restart Delay
Active
True when the Restart Delay timer is timing out.
Status Input
Run Input
True when the DGC-2020ES is indicating that the
Run relay should be closed.
Status Input
Run Mode
True when the DGC-2020ES is in Run Mode or the
Run Mode logic element is true.
Status Input
Single Phase
Connection
Override
True when the Single Phase Override input is true.
Status Input
Switch not in
Auto
True when the DGC-2020ES is not in Auto Mode.
Status Input
Start Input
True when the DGC-2020ES is indicating that the
Start relay should be closed to start the engine.
Output Objects
Physical
Outputs
OUT1 – OUT4
Physical Outputs 1 through 4.
Remote
Outputs
OUT5 – OUT28
Remote Outputs 5 through 28.
(Available when an optional CEM-2020 is
connected.)
Alarms
Auto Restart
Fail
True after the Automatic Restart function fails to
restart the generator.
Battery Charger
Fail
True when the Battery Charger Fail function is
configured as an alarm and the activation delay has
expired.