Troubleshooting DGC-2020ES
The following parameters are visible on the CEM DEBUG screen:
DGC TO CEM BP: DGC-2020ES to CEM-2020 Binary Points. This is the status of the CEM-2020
output relays being transmitted from the DGC-2020ES to the CEM-2020. This is a 32-bit, bit packed
number representing the desired states of the CEM-2020 outputs. The left most bit is the first output,
etc.
CEM TO DGC BP: CEM-2020 to DGC-2020ES Binary Points. This is the status of the CEM-2020
inputs being transmitted from the CEM-2020 to the DGC-2020ES. This is a 32-bit, bit packed number
representing the metered states of the CEM-2020 inputs. The left most bit is the first input, etc.