Installation
Instruction handbook b maXX 5000
Document No.: 5.09021.16
125
of 328
7
Danger from
residual energy
DANGER!
Risk of fatal injury from elec
trical current!
Stored electric charge.
Discharge time of the modular system = discha
rge time of the device with the longest
DC link discharge time in the modular system.
Refer to ZElectrical da
taas from page 58.
Therefore:
m D
o not touch before taking into account the discharge time of the capacitors and
electrically live parts.
m He
ed corresponding notes on the equipment.
m If ad
ditional capacitors are connected to the DC link, the DC link discharge can
take a much longer time. In this case, the necessary waiting period must itself be
determined or a measurement made as to whether the equipment is de-energized.
This discharge time must be posted, together with an IEC 60417-5036 (2002-10)
warning symbol, on a clearly visible location of the control cabinet.
7.2 Voltage test
DANGER!
Risk of fatal injury from electrical current!
During the routine test of these devices, a voltag
e test is performed by Baumüller
Nürnberg GmbH in accordance with EN 61800-5-1, Section 5.2.3.2. It is thus unnec-
essary for the customer to do
this.
Therefore:
m Subse
quent tests of the devices using high voltages may only be performed by
Baumüller Nürnberg GmbH.
m Di
sconnect the device from the system during high-voltage testing!