EasyManua.ls Logo

Baumuller BUG 622 - Control terminals

Baumuller BUG 622
58 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
Basic Supply Unit BUG 622, 623 39
Baumüller Nürnberg GmbH 5.94034.07a
5.5.2 Control terminals
y All control voltages applied externally must comply with the regulations for PELV or SELV
y Sub-unit terminal X99A/X99B
All terminals are connected to each other. Because of this they can be used as BUS-connection from
one Baumüller unit to the other.
The signals can be executed as a bus connection, due to the connection of X99A with X99B of the next
unit in the line.
Recommended connection lead length 44 mm:
X 99 A
X 99 B
Terminal no. Assignment
1, 2 + 24 V (PELV)
Terminal for power supply to the units,
both terminals internally bypassed,
2nd terminal with power supply current > 10 A
3, 4 Ground 24 V (PELV)
Terminal for power supply to the units,
both terminals internally bypassed,
2nd terminal with power supply current > 10 A
5 Ready for use, internal (PELV)
Ready for use message from the supply
converter to all units attached to the DC link.
6
Reserve (PELV)
WARNING
A maximum current greater than 10 A per single terminal may cause damage to the equipment.
If higher currents are needed do build a multiple feeder system.

Related product manuals