3-4
3. Preparations for a Test
Set timer
After a preset period
the high voltage is switched off
The discharge device of the PGK50/80 can be activated by
switching off the high voltage manually or by the timer.
Set timer before or during a high voltage test.
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
T / min
grrr...
Turn knob to desired period
After the preset period (0-30
minutes):
- an acoustic signal is
activated.
- the high-voltage is
switched off.
- the discharge device is
activated.
Option: After preset period activate
acoustic signal only
If desired that after the preset period the high voltage is not
switched off and only the acoustic signal is activated:
Please refer to Section 5. Maintenance / Timer - activate acoustic
signal only.