6
1 Application
Syscompact 2000 is a compact designed, fully enclosed cable fault location system for
prelocation and pin pointing of high impedance, low impedance and intermittent cable faults
of low and medium voltage cables. Easy operation and use of latest fault location methods in
combination with efficient instruments enable a rapid and reliable fault location.
The equipment is available with a surge generator SSG 1100, 1500 or 2100. Optionally a
SSG 500 could be integrated. The compact design of the equipment enables easy transport
and installation into every van with a payload of 300 to 500 kg.
Cable fault location
For all measuring methods the preset and evaluation parameters have an automatic function.
After starting the automatic function, a completely evaluated echogram is displayed on the
screen. The operator is presented with a complete analysis of the trace. Manual set up of
measurement parameters is also possible. Print out of trace and data is realized via report
and print function.
Cable fault location methods
• Pulse Reflection Method (TDR)
• Secondary Impulse Method (SIM)
• Multiple Impulse Method (SIM – MIM)
(advanced SIM)
• Differential Secondary Impulse Method
• Impulse Current Method (ICM)