9 Settings
Combi 2
53
9
Settings
9.1
Accessing the settings
Fig.62 Step 2
To display/change the list of SERVICE settings, proceed as follows:
press the F3 key, the symbol on the menu bar starts to flash;
turn the
knob until you reach the symbol to access user settings,
symbol to access installer settings, then
knob to enter code 0012
turn the
key to confi
rm;
To view/modify the list of settings, it is also possible to connect the
Bluetooth interface to the boiler via the connector X10. Then interface the
handset (SERVICE) to the boiler using the SERVICE TOOL software.
9.2
List of parameters
Important
The factory settings for certain settings may differ based on the
market the product is destined for.
Tab.26 Table of parameters
Name
Description
Minimum
Maximum
Level
AP001
Operation of contact X15 (also see setting AP098)
1: Contact open —> Heating, domestic hot water and
antifreeze disabled (error code H02.10)
2: Contact open —> Heating, domestic hot water
disabled (error code H02.09)
3: Contact open —> Heating, domestic hot water and
antifreeze disabled (error code E02.13 with reset
request)
2
– – Installer
AP002
Manual heating request enabled based on
implementation of setting AP026
0: Disabled
1: Enabled
0
– – Installer
AP006
Notification of low pressure in the heating installation
[bar]
0.8 0.6 3.0 Installer
AP009
Hours of burner ignition before the maintenance
notification with AP010=1
3000
0
51,000 Installer
AP010
Enables/disables maintenance notifications:
0: No notification
1: Customised notification (depending on settings
AP009 and AP011)
0
– – Installer
Danger
FOR LOW TEMPERATURE HEATING INSTALLATIONS
MODIFY SETTING CP000 ACCORDING TO THE MAXIMUM
FLOW TEMPERATURE.
turn until you reach the
press the key to confirm;
if accessing the installer menu, use
the and confirm by pressing the key
knob until you reach the desired setting, then press the
knob;modify the value of the setting using
the press to confirm;
press to exit.