Function Profile Description
26.XX
Pull-in safety device
CLOSE
If the pull-in safety device signals during travel, the error code E.343 appears and the door is
stopped. In the case of pull-in safety CLOSE, the CLOSE travel is blocked. Travel in the opposite dir-
ection is possible in dead-man mode. A triggered pull-in safety device is acknowledged in the CLOSE
limit position. In order to achieve Category 2 according to EN 13849-1, testing is necessary using a
switching output and the "External testing" function.
26.00 NC – normally closed | External testing
26.01 NC – normally closed | Without testing
27.XX
External switching input
If this is activated, drive commands are blocked.
27.00 NC – normally closed | Close automatically, all drive commands blocked
27.01 NO – normally open | Close automatically, all drive commands blocked
27.02 NC – normally closed | CLOSE limit position: All drive commands blocked
27.03 NO – normally open | CLOSE limit position: All drive commands blocked
27.04 NC – normally closed | CLOSE limit position: All drive commands blocked, except for the
keypad on the cover
27.05 NO – normally open | CLOSE limit position: All drive commands blocked, except for the
keypad on the cover
27.06 NC – normally closed | Keyboard on cover blocked
27.07 NO – normally open | Keyboard on cover blocked
27.08 NC – normally closed | Invisible drive commands blocked
27.09 NO – normally open | Invisible drive commands blocked
27.10 NC – normally closed | Drive commands blocked externally
27.11 NO – normally open | Drive commands blocked externally
27.12 NC – normally closed | Radio is blocked
27.13 NO – normally open | Radio is blocked
28.XX
Drive command sequence
– 3
Open / limit position /
close / open
For radio, only "Door visible = No" can be parameterised. An NO – normally open contact must be
used as the contact type.
Maintained operation
The commands are executed one after the other in the sequence OPEN / LIMIT POSITION / CLOSE /
OPEN.
Dead-man
The CLOSE command is only executed when in the OPEN or partial opening limit position. If the com-
mand is active for more than 60 s, the error code I.119 appears and the command is ignored. If the
door is visible: No, dead-man operation is not possible.
28.00
28.11
See drive command OPEN
29.XX
Fault display input
The input can be used to display an error of an external device (e.g. warning light).
29.00 NC – normally closed | No travel, F.850
29.01 NO – normally open | No travel, F.850
29.02 NC – normally closed | Dead-man, E.851
29.03 NO – normally open | Dead-man, E.851
29.04 NC – normally closed | Information I.852
29.05 NO – normally open | Information I.852
25

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Becker BDC-i440 Series and is the answer not in the manual?

Becker BDC-i440 Series Specifications

General IconGeneral
BrandBecker
ModelBDC-i440 Series
CategoryControl Unit
LanguageEnglish

Related product manuals