P. [Unit] Setting
range
Description Ex works
950
[Inc]
0..4095
Current position
In this parameter, the current position of the door in relation to the CLOSE limit po-
sition is displayed.
0
973
0..1
Resetting the maintenance counter
The maintenance counter is confirmed by setting this parameter to 1.
0
980
0..5
Operation mode
With this parameter, the operation mode of the control unit is set. The following
modes are possible:
0: Travel in the OPEN and CLOSE directions in maintained operation mode (auto-
matic)
1: Travel in the OPEN direction in maintained operation mode, travel in the CLOSE
direction in manual mode (semi-automatic)
2: Travel in the OPEN and CLOSE directions in manual mode (dead-man)
3: Travel in the OPEN and CLOSE directions in manual mode without a safety edge
SE1 (dead-man)
4: Dead-man emergency travel (no safety devices active/no limit positions)
5: Inching mode (no safety devices active/no limit positions)
0
985
0..1
Language of the display text
Sets the language of the display text:
0: English
1: German
1
990
0..4
Factory setting
By setting and saving this parameter, parameters or programmed positions are
deleted:
0: No reset
1: Set parameters to factory setting of the current door profile
2: Delete programmed positions
3: Set parameters to factory setting of the current door profile and delete pro-
grammed positions
4: Reset door profile, set parameter to factory setting and delete programmed po-
sitions
0
991
0..x
Selection of the door profile
0: Mechanical limit switching (Becker-Antriebe GmbH)
1: Mechanical limit switching (Becker-Antriebe GmbH)
2: Absolute value encoder (Becker-Antriebe GmbH)
3…X Customised door profiles, see chapter "Door profiles"
-
992
0..x
Selection of the function profile
0: No selection
1: M1 two-way traffic control
2: M2 two-way traffic control
0
999
0000..FFFF
Password
(1)
Password for selecting the parameterisation level
By means of the different password levels, access is granted to varying numbers
of parameters.
Changing parameters without knowledge of their function is prohibited.
In order to avoid errors and hazards caused by unauthorised access, passwords
must only be given to trained personnel.
0
(1)
This parameter is accessible after toggling the DIP switch PAR = ON.
46