Product overview
EK110x, EK15xx26 Version: 3.6
if the EtherCAT master supports HotConnect, then an I/O group can be adopted dynamically into the
EtherCAT communication. This group can then be located at any position within the EtherCAT network.
Variable topologies are therefore easily implementable.
Quick links
EtherCAT basics [}31]
Application notes [}56]
Diagnostic LEDs [}66]
2.4.1.2 EK1501 - Technical data
Technical data EK1501
Task within the EtherCAT system Coupling of EtherCAT Terminals (ELxxxx) to
100BASE-FX EtherCAT networks
Number of EtherCAT Terminals up to 65535 in the overall system
Number of peripheral signals max. 4.2GB addressable IO points
Transmission medium Multimode glass fiber (MM)
Cable length between two Bus Couplers max. 2km (100BASE-FX)
Transceiver wavelength typically 1300nm
Protocol / Baud rate EtherCAT Device Protocol / 100MBaud
HotConnect max. number of configurable IDs: 4096
Delay typical 1µs
Bus connection 2 x SC Duplex
Power supply 24V
DC
(-15%/+20%)
Current consumption 130mA + (E-bus current)/4
E-bus power supply (5 V)
depending on ambient temperature
(at higher current consumption the EL9410 power
feed terminal can be used in addition)
max. 2000mA (-25°C ... +55°C)
max. 1000mA (> +55°C)
Power contacts max. 24V
DC
, max. 10A
Electrical isolation 500 V (power contact/supply voltage/EtherCAT)
Dimensions (W x H x D) approx. 49mm x 100mm x 70mm
Weight approx. 190g
Permissible ambient temperature range during
operation
-25°C ... +60°C (extended temperature range)
Permissible ambient temperature range during
storage
-40°C ... + 85°C
Permissible relative humidity 95%, no condensation
Mounting [}37]
on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2 / EN 61000-6-4
Protection class IP20
Installation position variable
Approval CE
ATEX [}54]
cULus [}52]

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Beckhoff EK1100 and is the answer not in the manual?

Beckhoff EK1100 Specifications

General IconGeneral
Product TypeEtherCAT Coupler
Number of Ports2
FieldbusEtherCAT
Bus InterfaceEtherCAT
Protection ClassIP20
Max. Current Supply for the E-bus2 A
Electrical Isolation500 V (E-bus/Fieldbus)
Weightapprox. 150 g
Relative Humidity95%, no condensation
Vibration/Shock ResistanceConforms to EN 60068-2-6/EN 60068-2-27
EMC Immunity/EmissionConforms to EN 61000-6-2/EN 61000-6-4
Approvals/MarkingsCE, UL, ATEX, IECEx
Power Supply24 V DC (-15%/+20%)
Operating Temperature-25°C to +60°C
Storage Temperature-40°C to +85°C
Current Consumption Power Contacts10 mA
Number of I/O Modules64
Installation Positionany