Control 1.3 Swimming Pool Control Unit
Operation
28
Figure 4: Backwashing setting
In field you choose the backwash valve type. You can choose between a rod valve and a Badutronic
valve.
In field you set the running time of the backwashing.
The control unit can only be operated together with a Badutronic 93 and Omnitronic. The rod valve must be
connected to the output A6. The Badutronic must be connected to the inputs E1 and E10 and to the output
A6.
You need to go to the Treatment Filter Cleaning Pause submenu and select the desired pause time
here (max 200 s) to set the pause in order to adjust the rod valve. This time also applies for a possible rinse
valve.
Rinsing Setting
You need to go to the Treatment Filter Cleaning Rinsing Setting submenu to set the rinsing
parameters. This has the same layout as the Backwashing Settings submenu (Figure 4).
In field you select whether a rinse valve (3-way rod valve) is connected.
In field you set the running time of the rinsing cycle.
The rinse valve must be connected to the output A7.
Pause
You need to go to the Treatment Filter Cleaning Pause submenu to pause the filter pump in order
to adjust the backwash valves. Here the pause time is entered in seconds (max. 200 sec).
Forced Overflow Channel