Safety Precautions
Warning:
Do not disconnectequipment unless power has been removed or thearea is
knownto be non-hazardous
AVANT DE DECONNECTER L’EQUIPEMENT, COUPER LE C OURA NT
OUS’ASSURER QUE L‘EMPLACEMENT EST DESIGNE NON DANGEREUX.
Warning:
Only UL and cUL approved expansion units are allowed to be connected to
the port designated“EXPANSION”. Atthe momentthere are no such units
evaluated or a llowed.
SEULES LES UNITÉS D'EXTENSION CERTIFIÉESUL ET
cUL PEUVE NT ÊTRE RACCORDÉES AU PORT DÉSIGNÉ « EXPANSION ».
À L'HEURE ACTUELLE, AUCUNE UNITÉDE CE TYPE N'A ÉTÉ TESTÉE
OU AUTORISÉE.
Warning:
Do not replaceexpansion unit unless power has been switchedoff or thearea
is known to be non-hazardous.
NE REMPLACEZ L'UNITÉ D'EXTENSIONQUE SI LE
COURANT A ÉTÉ COUPÉ OU SI LA ZONE E ST JUGÉE NON DANGEREUSE.
• This product contains a battery; this must only be cha
nged in an area known
to be non-hazardous.
• Replace the battery with a CR2450 battery. Us
e of another type of battery
may present a risk of fire or explosion.
Warning:
Batterymay explode if mistreated. Do not recharge, disassemble or dispose
of in fire.
LA BATTERIE PEUT EXPLOSER EN CAS DE MAUVAISE MANIPULATION.
NE LA RECHARGEZ PAS, NE LA DÉMONTEZ PAS ET N E LA JETEZ
PAS DANS LE FEU.
• For use on a flat surface of a type 4X enclosure indoor use only.
• Use minimum 75°C copper conductors only.
• To make wiring connections to the power supply connector, follow the table
with cable and torque specifications below:
Terminal Block Connector Wire Size TQ Lb.In.
X1/X100 Phoe n ix connectors AWG 30–12 5–7
X1/X100 Anytek connectors AWG 24–12 3.5
• These dev
ices are Class 2 supplied programmable controllers (industrial PCs)
for the u
se in industrial control equipment and are intended to be (front)
panel mo
unted (Type 1 and 4x for indoor use only).
Beijer Electronics, MAEN774E
5