VRP-M VAV
Adaptive VAV controller
www.belimo.eu Product information S4-VRP-M VAV • en • v2.0 • 11.2006 • Subject to changes 11 / 28
Functions
(Continued)
Note
mid
is not available with DC 24 V supply.
VAV override operation
CLOSED /
min
/
mid
/
max
/ OPEN
If necessary, the VAV
min
...
max
range can be overridden by fixed operating steps in VAV ap-
plications.
The following operating steps are available:
– Shut-off operation – damper CLOSED: The damper is moved into the CLOSED position in a
defined manner.
– Operating steps
min
/
mid
/
max
: The VRP-M adjusts the volumetric flow to the fixed selected
value.
–
Flushing operation – damper OPEN: The damper can be opened for maximum ventilation, in
which case air volume control is deactivated.
Note
–
min
: All inputs (3 / 6 / 7) open.
–
mid
is not available with DC 24 V supply.
Priorities for reference value input 3 (w)
and control inputs 6 (z1) / 7 (z2)
If several signals appear simultaneously, they are processed acc. to the following priorities:
Terminal Priority Function
6 z1 1 OPEN
7 z2 2 CLOSED /
min
/
mid
/
max
3 w 3
min
…
max
Reference signal w
[V]
CAV operating mode
OPEN
(depending on supply pressure)
nom
max
mid
min
CLOSED
[
min
]
Volumetric flow [%
nom
]
[
max
]
Volumetric flow [%
nom
]
[
max
]
ZU
OPEN
nom
max
mid
[
min
]
Constant operation
Variable operation
Constant operation
min
Volumetric flow actual value signal U5 [V]
Example: 2 ... 10 V mode