Operation and setting
34
TGH1410en/03.2012
5.6 Commissioning
Prior to commissioning, check proper connection of the residual current mon-
itor.
5.7 Factory setting
5.8 Standards, approvals and certifications
Response value overcurrent I1 (prewarning)
Response value overcurrent I2 (alarm)
Hysteresis:
Fault memory M:
Operating mode K1/K2
Starting delay:
Response delay:
Delay on release:
Transformer correction factor n (n
RCM
)
Password:
15 mA (50 % of I2)
30 mA
15 %
activated (on)
N/C operation (n.c.)
t = 0.5 s
t
on1
= 1 s
t
on2
= 0 s
t
off
= 1 s
1
0, deactivated (Off)