Technical data
3-1
3 Technical data
3.1 General characteristic features
• Self-control to verify flawless function of the de-
vice in keeping with European standard
EN298:2012.
• Two spectral bands separately adjustable
• Selective amplifiering of gas and oil firing sys-
tems
• Si and PbS sensor
• Fully electronic construction
• Spectral analyzing process
• Tested by the German Technical Inspection As-
sociation TÜV
• Approved of by DIN DVGW
• Suitable for safety related applications up to SIL
3 (according to IEC 61508) in combination with
flame amplifier 3001 / 3001D / 3001S
3.2 Electrical system, optical system, me-
chanical system
Description Value
Spectral sensitivity 300 bis 2700nm
Angle view 2.7 degrees in combination with SKL
Self-monitoring Full electronical,
1 x in a second
Supply voltage 24 V DC
Current consumption approx. 200 mA
Design in accord. with protection class III SELV
Ambient temperature
Electronic
Fibre optic cable
-20 °C to +70 °C
(-4 °F to +160 °F)
-20 °C to +200 °C
(temporary up to +300 °C)
(-4 °F to +390 °F )