4.7.4 Laying the special cable KW5 for Ex-
housing (ATEX Zone 1)
The outer braided shield shall be clamped
between clamp collar I & II on the scanner side.
Assembly:
First the cable and the clamp collars must be
fixed with screwed cap I.
On the second stage the PUR sheath must
be tightend with screwed cap II.
The inner screening shall be cut of on the scanner
side and connected to ground at the flame controler.
No.
Item
No.
Item
1 Screwed coupler 8 Screwed cap 2
2 Rubber casket 1 9 PUR cable sheath
3 Clamp collar 1 10 Ex de IIC housing
4 Outer braided shield 11 wire end ferrule
5 Clamp collar 2 12 heat-shrinkable tu-
bing
6 Screwed cap 1 13 cable gland
Reg.-No.: Ex-dIIC
ISSEP 96D.103.1226
7 Rubber casket 2