EasyManuals Logo

BFI Automation CFC 2000 User Manual

BFI Automation CFC 2000
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #43 background imageLoading...
Page #43 background image
Description
5-3
5.3.2 Safety switch-OFF time of the safety channel
The safety switch-OFF time of the safety channel (hard-
ware) is set by means of a jumper. The settings are as fol-
lows:
Jumper 1 bridged: 1 second
Jumper 2 bridged: 3 seconds
Jumper 3 bridged: 5 seconds
If a switch-OFF time of 2 seconds is required, the jumper
must be inserted in position 2 (3 seconds) and the switch-
OFF time of the evaluation channel set by software to 2
seconds (see Handbook HB CFC Com1 EN). The shorter
switch-OFF time of the two channels always takes priority.
The safety switch-OFF time during operation (shut-off
time) is also dependent on the software setting (see
Handbook HB CFC Com1 EN)!
Jumper 1-3

Table of Contents

Other manuals for BFI Automation CFC 2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the BFI Automation CFC 2000 and is the answer not in the manual?

BFI Automation CFC 2000 Specifications

General IconGeneral
BrandBFI Automation
ModelCFC 2000
CategoryController
LanguageEnglish

Related product manuals