5.3.2 Safety switch-OFF time of the safety channel
The safety switch-OFF time of the safety channel (hard-
ware) is set by means of a jumper. The settings are as fol-
lows:
Jumper 1 bridged: 1 second
Jumper 2 bridged: 3 seconds
Jumper 3 bridged: 5 seconds
If a switch-OFF time of 2 seconds is required, the jumper
must be inserted in position 2 (3 seconds) and the switch-
OFF time of the evaluation channel set by software to 2
seconds (see Handbook HB CFC Com1 EN). The shorter
switch-OFF time of the two channels always takes priority.
The safety switch-OFF time during operation (shut-off
time) is also dependent on the software setting (see
Handbook HB CFC Com1 EN)!