Logic Denition
Default
Cross out
setting
used
Optional extras
EXPI2
Conguration of
EXPI2 input
on input-output
expansion board.
1-3
0
0 Input congured as Start E command.
1 Input congured as Start I command.
2 Input congured as Open command.
3 Input congured as Close command.
4 Input congured as Ped command.
5 Input congured as Timer command.
6 Input congured as Timer Pedestrian command.
7 Input congured as Phot (photocell) safety.
8 Input congured as Phot op safety (photocell active during opening only).
9 Input congured as Phot cl safety (photocell active during closing only).
10
Input congured as Bar safety (safety edge).
11
Input congured as safety Bar OP, safety edge with inversion active only while opening, if while closing
the movement stops.
12
Input congured as safety Bar CL, safety edge with inversion active only while closing, if while opening
the movement stops.
EXPO1
Conguration of
EXPO2 output
on input-output
expansion board
4-5
11
0 Output congured as monostable Radio Channel.
1 Output congured as SCA (gate open light).
2 Output congured as Courtesy Light command.
3 Output congured as Zone Light command.
4 Output congured as Stair Light.
5 Output congured as Alarm.
EXPO2
Conguration of
EXPO2 output
on input-output
expansion board
6-7
11
6 Output congured as Flashing light.
7 Output congured as Latch.
8 Output congured as Magnetic lock.
9 Output congured as Maintenance.
10 Output congured as Flashing Light and Maintenance.
11 Output congured as Trac Light control with TLB board.
12
Not used
13
Output congured as Gate Status
14
Output congured as Bistable Radio Channel
15
Output congured as timed Radio Channel
TRAFFIC LIGHT
PREFLASHING
Trac light pre-
ashing
0
0 Pre-ashing switched o.
1 Red lights ash, for 3 seconds, at start of operation.
TRAFFIC LIGHT
RED LAMP
ALWAYS ON
Steadily lit red light 0
0 Red lights o when gate closed.
1 Red lights on when gate closed.
* Only active on FW > 1.12
Radio channel control conguration
CH logic= 0 - Control congured as Start E. Operation according to STEP-BY-STEP MOV. logic. External start for trac light control.
CH logic= 1 - Control congured as Start I. Operation according to STEP-BY-STEP MOV. logic. Internal start for trac light control.
CH logic= 2 - Control congured as Open.
The command causes the leaves to open.
CH logic= 3 - Control congured as Closed.
The command causes the leaves to close.
CH logic= 4 - Control congured as Ped.
The command causes the leaf to open to the pedestrian (partial) opening position. Operation according to STEP-BY-STEP. logic
Logica CH= 5- Control congured as STOP.
The command performs a STOP
CH logic= 6 - Control congured as AUX0. (**)
The control activates the AUX0 output
CH logic= 7 - Control congured as AUX1. (**)
The control activates the AUX1 output
CH logic= 8 -Control congured as AUX2. (**)
The control activates the AUX2 output
CH logic= 9 - Control congured as AUX3. (**)
The control activates the AUX3 output
CH logic= 10 - Control congured as EXPO1. (**)
The control activates the EXPO1 output
CH logic= 11 - Control congured as EXPO2. (**)
The control activates the EXPO2 output
(**) Active only if the output is congured as Monostable Radio Channel, Courtesy Light, Zone Light, Stair Light, Bistable Radio Channel or Timed Radio Channel.