EasyManuals Logo

BIFFI ICON3000 Advanced Maintenance Instructions

BIFFI ICON3000
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #33 background imageLoading...
Page #33 background image
Installation, Operation and Maintenance Manual
MDE 257 Rev. 1
March 2021
29
Alarm "Conguration n°"
Section 4: Alarm "Configuration n°"
Operation Log
Table 40. General Log
Maintenance
Obj n° Value Function Description
924 10 Opening time Seconds, Read-only
925 10 Closing time Seconds, Read-only
920 1200 Contactor cycles Resolution 100, Read-only
922 1020 Motor run time Hours, Read-only
928 300 No power time Hours, Read-only
926 13 Utilization rate %, Read-only
956 -30 Min. temperature °C, Read-only
957 70 Max. temperature °C, Read-only
958 -34 Min. terminal board temperature °C, Read-only
959 72 Max. terminal board temperature °C, Read-only
961 80 Max. motor temperature °C, Read-only
964 2 Motor thermostat alarms Read-only
965 2 Torque alarms Read-only
Table 41. Recent Log
Maintenance
Obj n° Value Function Description
921 0 Recent contactor cycles Resolution 100, Read-only
923 0 Recent motor run time Hours, Read-only
929 0 Recent no power time Seconds, Read-only
927 0 Recent utilization rate %, Read-only
950 0 Recent min temperature °C, Read-only
951 0 Recent max temperature °C, Read-only
952 0 Recent min term. board temper. °C, Read-only
953 0 Recent max term. board temper. °C, Read-only
955 0 Recent max motor temperature °C, Read-only
962 0 Recent motor thermostat alarms Read-only
963 0 Recent torque alarms Read-only
964 2 Motor thermostat alarms Read-only
965 2 Torque alarms Read-only

Other manuals for BIFFI ICON3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the BIFFI ICON3000 and is the answer not in the manual?

BIFFI ICON3000 Specifications

General IconGeneral
BrandBIFFI
ModelICON3000
CategoryControl Unit
LanguageEnglish

Related product manuals