ST-150-4 51
5.7 Wiring in the state of delivery
Interventions on components that are delivered wired
and on their electrical connections are not necessary.
They are fully installed and wired at delivery:
5.7.1 HS.95: pre-fitted components
Slider position indicator (B70)
Solenoid valves for capacity control and V
i
(M11,
M12, M15 and M16)
Low pressure and high pressure transmitters (B51
and B50)
Discharge gas temperature sensor (B02)
Oil monitoring (OLC-D1, B30)
Oil pressure transmitter (B54)
Motor temperature monitoring (B03 to B08)
Rotation direction monitoring
5.7.2 CSW105: pre-fitted components
Slider position indicator (B70)
Solenoid valves for capacity control and V
i
(M11,
M12, M15 and M16)
Low pressure and high pressure transmitters (B51
and B50)
Oil temperature sensor (B02)
Monitoring of the minimum oil level (OLC-D1, B30)
Oil heater (E01) at 230 V voltage supply
Motor temperature monitoring (B03 to B08)
Rotation direction monitoring
5.7.3 OS.95: pre-fitted components
Slider position indicator (B70)
Solenoid valves for capacity control and V
i
(M11,
M12, M15 and M16)
Low pressure and high pressure transmitters (B51
and B50)
Discharge gas temperature sensor (B02)
Oil monitoring (OLC-D1, B30)
Oil pressure transmitter (B54)
5.7.4 OS.85: pre-fitted components
Solenoid valves for 4-step capacity control (M11,
M12, M13 and M14)
Low pressure and high pressure transmitters (B51
and B50)
Discharge gas temperature sensor (B02)
Oil supply monitoring (B42)
Oil filter monitoring (B42)
5.8 High pressure switch
According to EN378, each compressor must be
provided with a high pressure switch (B10) for safety
cut-out in the safety chain. Depending on the displace-
ment and refrigerant charge, it must be designed as a
safety pressure cut-out and / or only as pressure cut-
out. The software-controlled monitoring of the com-
pressor module via the high pressure transmitter (B50)
does not sufficiently ensure the safety cut-out function.
The high pressure switch (B10) should preferably be
connected to terminal strip CN3. The data are analysed
and logged in this case.
The installation of a low pressure switch is not neces-
sary, depending on local regulations. The compressor
module is provided with an automatic low pressure cut-
out function.

Table of Contents

Other manuals for Bitzer CM-SW-01

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bitzer CM-SW-01 and is the answer not in the manual?

Bitzer CM-SW-01 Specifications

General IconGeneral
BrandBitzer
ModelCM-SW-01
CategoryControl Unit
LanguageEnglish

Related product manuals