SB-170-10 79
FI current bars at CSV.
Size
M10 56 Nm
Mount the screwed connection in this order: screw,
washer, FI connection, current bar, pair of wedge lock
washers, nut.
10.4 Special screwed connections inside the
compressor
Assess the risk of conversion and take appropriate
measures before any intervention into the compressor.
Before re-commissioning: Test the compressor de-
pending on the risk assessed for pressure strength and
tightness or for tightness only.