BL6-U Parallel Integrated Controller Quick Commissioning User Manual
38
Time Setup Parameters List
Brake open first then run elevator speed
curve. This is to improve the elevator start
comfort and match control system with
different machine brake on time.
Brake close first then disable elevator run.
This is to improve elevator stop comfort
and avoid slip at elevator stop.
The time delay in inspection mode before
brake close.
The time delay when system detects
elevator stop. Adjust this parameter to
close brake after elevator reach 0 speed
completely, increase elevator stop comfort.
In Auto mode, elevator automatically open
door when stopping at one floor, door will
automatically close after set time.
Enable door open delay function, press
open delay button, door open time will be
delayed.
The waiting time before elevator return to
homing floor without landing/car call, set
value to “0” to disable this function.
1. The door open/close command run time;
2. Door open/close relay run time for door
drive without open/close limit switch.
3. For door drive with open/close limit
switch, this run time should be 1s longer
than the door actual open/close time.
After elevator change speed to target floor,
landing signal is delayed by set time, arrival
gong /voice synthesizers are also delayed
by set time.
Drive enable signal given/drop is delayed
by set time after drive direction signal is
given/drop. During this time, drive output
current is decreased to reduce current
noise.
In Auto mode, if have no car/landing call
during set time, system will cut car light
power from COP.
To prevent wire rope slipping or elevator
car stuck, time from elevator running to
stop is limited to set value. If elevator is
running longer than set value, system stops
immediately and enter protection mode.
Need to re-start the system in order to exit
from such mode.
The time to keep elevator start smooth.
System will automatically start the elevator
(Electric lock: ON) at set time.
System will automatically stop the elevator
(Electric lock: OFF) at set time. This
function is disabled if same start/stop time.