Installation and start-up of INGENIO PLUS UPS 30÷40 kVA
Installazione e avviamento INGENIO PLUS UPS 30÷40 kVA
36 OMS02082 REV. D
4.4.1.2 60 x 12 Ah 12V installation –INGENIO PLUS 30-40 kVA
1) Remove the four screws to open the front cover and access the battery trays
(total trays are 6 and each contain 10 batteries, see picture 13 & 14).
Picture 13 - Trays 60 x 12Ah 12V battery lateral view
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
1*
2 *
LINK 1* AND 2* ARE NOT CONNECTED FOR SHIPMENT SAFETY REASON. THIS CABLES
MUST BE CONNECTED OLNLY DURING THE INSTALLATION.
Picture 14 – Tray 60 x 12Ah 12V battery top view
READ
INDICATIONS
FOR HANDLING
BATTERY TRAYS
AT PAGE 33