66 en | Maintenance – walktest
FPA-5000 | FPA-1200 | AVENAR panel 8000 |
AVENAR panel 2000 | AVENAR keypad 8000
2020-07 | 3.0 | F.01U.378.877 User Guide Bosch Sicherheitssysteme GmbH
Show / Change: Delete all elements in the selected walk test group and delete
individual elements.
Add: Display all elements that have not yet been assigned to a walk test group, and
add individual elements.
Cancel: Cancel the operation.
Notice!
The deleted elements are assigned to the Unassigned elements group.
Toggle function
New elements can be added and existing elements deleted in every submenu.
Add
When one of the function fields is selected, the display changes and a new function can be
performed.
+
New
Select this function field to add one or more new elements.
Only those elements which have not been assigned to any walktest group yet will be
displayed.
Various element categories are displayed.
1. Select the category you require.
A list of elements is displayed. See also
Working with lists, page 24
.
2. Select an element.
The element is marked.
3. Select Add.
The selected element is added to the group.
Delete
-
Old
Select this function field to delete one or more elements.
Only elements from the selected walktest group are displayed.
1. Select an element.
The element is marked.
2. Select Delete.
The selected element is deleted from the group.
Example:
1. Select Show / Change.
To delete one or more element(s) from the selected group:
2. Select one or more list fields.
The list fields are marked. Refer to
Scrolling through lists, page 25
for information on how
to navigate through a list.
3. Select Delete.
The element is deleted from the selected group. The list field is no longer displayed.