32.4 Cross points
Points can be assigned to cross point groups. When a point in a cross
point group detects an alarm, the control panel starts the cross point
timer. If a second point in the same cross point group detects an alarm
while the cross point timer is active, the control panel sends alarm
reports for both points.
If a single cross point detects an alarm and stays in alarm throughout
the cross point timer, the control panel sends an alarm report only for
that point. If a single point in a cross point group detects an alarm and
restores while the timer is still active, the system sends an unverified
event for that point. A second alarm on the first point does not create
an alarm event, but rather an unverified event.
Cross points are:
enabled on my system.
disabled on my system.