RDCI Series – All DC Inverter Outdoor Units
32 | F-Gas information
Model Product Description
N.Cooling
Capacity
N.Heating
Capacity
Refrigerant GWP
CO2
equivalent
for pre-
charged
refrigerant
Pre-
charged
Refrigerant
Amount
Additionally
Charged
Refrigerant
Overall
amount of
refrigerant
after
charging
Overall CO2
equivalent
after charging
[kW] [kW] - - [tonnes] [kg] [kg] [kg] [kg]
RDCI8/25-3 Outdoor Unit, 3-pipe, 3ph 25,2 27 R-410A 2088 20,9 10
RDCI10/28-3 Outdoor Unit, 3-pipe, 3ph 28 31,5 R-410A 2088 20,9 10
RDCI12/33-3 Outdoor Unit, 3-pipe, 3ph 33,5 37,5 R-410A 2088 20,9 10
RDCI14/40-3 Outdoor Unit, 3-pipe, 3ph 40 45 R-410A 2088 27,1 13
RDCI16/45-3 Outdoor Unit, 3-pipe, 3ph 45 50 R-410A 2088 27,1 13
Frequency of Refrigerant Leak Checks
- If the amount of tons CO2 equivelant/circuit is from 5 to 50 tons, then frequency to check is 12 months
in case system is without a leakage dedection system or 24 months in case system is with a leakage
dedection system.
- If the amount of tons CO
2 equivelant/circuit is from 50 to 500 tons, then frequency to check is 6 months
in case system is without a leakage dedection system or 12 months in case system is with a leakage
dedection system.
- If the amount of tons CO
2 equivelant/circuit is over 500 tons, then frequency to check is 3 months
in case system is without a leakage dedection system or 6 months in case system is with a leakage
dedection system.