RDCI Series – All DC Inverter Outdoor Units
4 | OUTDOOR UNIT INSTALLATION
Do not install the outdoor unit in a dirty or severely polluted location,
to avoid blockages in the heat exchanger of the outdoor unit.
Do not install the outdoor unit in a location with oil pollution, high
salt content air or high content of harmful gases such as sulfurous
gas.
4.4 Base for outdoor unit
Base types
Steel structure base
Ensure you consult a construction engineer before installation.
Ensure the base has been installed to the correct dimensions set out
in this manual. Raise the unit at least 200mm from the floor.
Position illustration of screw bolt (Unit: mm)
Table.4-3 Unit: mm
HP
SIZE
816
A 1120
B 1250
C 736
D 765
Centering position illustration for each connective pipe (Unit: mm)
1) 8HP, 10HP
2) 12HP
Ø10 Expansion bolt
Rubber shocking
proof mat
Concrete base
h=200mm
Solid ground or
roofing
200 mm
Fig. 4-2
B
A
C
D
15×23long U-shape hole
Fig. 4-3
R
Fig. 4-4
250
205
245
290
230
205
200
170
Fig. 4-5
High-pressure
gas balance valve
Low-pressure gas
side of shut-off valve
High-pr
essure gas
side of shut-off valve
L
iquid side of
shut-off valve
Oil balance valve
R amplification
The connective pipe
diameter Ø19.1
The connective pipe
diameter Ø22.2
The connective pipe
diameter Ø19.1
The connective pipe
diameter Ø12.7
For the Cascaded Units
R
Fig. 4-6