6.8. Check the Leakage
Check all the joints with the leak detector or soap water.
6.9. Thermal insulation
Use appropriate thermal insulation for pipe insulation. Use thicker insulation
when installing in hot or humid conditions.
1. Use the thermal insulation with properties that can withstand 120 C.
7. WIRING
7.1. Electrical wiring
CAUTION
1. Ensure all power cable installation works are carried out by a qualified
electrician.
2. All equipment must be grounded and have a local isolation point.
3. Ensure when installing power cables they are installed in different
containment to communication cables.
4. If you have to extend the cable, make sure you use connective blocks or
connecting terminals.
5. Before turning on the power, ensure all terminals are connected securely.
7.2. Power specification
Use the table below for power cable selection.
Table 7-1
Item
Model
SBOX Power
Power supply Power switch
Capacity Safety fuse
SBOX01/
SBOX02
220-240V~
50Hz
5A 5A
SBOX04
220-240V~
50Hz
5A 5A
SBOX06
220-240V~
50Hz
5A 5A
SBOX02E
220-240V~
50Hz
5A 5A
SBOX04E
220-240V~
50Hz
5A 5A
Table 7-2
Item
Model
SBOX Power Wires
Power cable Signal wire
Power
wire
Grounding
wire
Wire diameter
SBOX01/
SBOX02
2mm 2mm
3-core shielded
wire 0.75mm
SBOX04 2mm 2mm
3-core shielded
wire 0.75mm
SBOX06 2mm 2mm
3-core shielded
wire 0.75mm
SBOX02E 2mm 2mm
3-core shielded
wire 0.75mm
SBOX04E 2mm 2mm
3-core shielded
wire 0.75mm
NOTE
The above parameters are only for guidance, ensure you adhere to
national wiring regulations.
7.3. Wiring for the SBOX power wire and signal wire
1. You must use a different power supply to the outdoor power supply.
2. For power terminal connection, use connections labelled L,N and E. For
communication wiring use terminals P,Q and E.
Cut it from up to down
Field piping side
Unit body
Subsidiary belt of thermal
insulation pump
Fig.6-7
10 | WIRING
6720862460 (16/04) CLIMATE 5000 VRF