3.2 Flue terminal positions
Use as a guide only. Refer to AS/NZ 5601 or gas fitting rules for specific
location.
Fig. 1 Flue terminal positions: Shaded area indicates prohibited area
D Door
I Mechanical air inlet
M Gas meter
T Flue terminal
W Window
The location of the flue terminal must comply with the clearances
shown on this page.
If you are unsure about clearances not indicated here, in general refer
to AS/NZ 5601 or your local authority.
All measurements are the minimum clearances required.
Terminals must be positioned so to avoid combustion products
entering the building.
f
c
n
k
k
j
jj
h
h
e
T
e
h
T
g
P
W
d
b
d
T
g
c
a
M
D
I
Ref. Item Min. Clearance
mm
a Below eaves, balconies and other projections (Appliances over 50MJ/h) 300
b From the ground, above a balcony or other surface 300
c From a return wall or external corner 300
d From a gas meter 1000
e From an electricity meter or fusebox/breaker panel 500
f From a drain pipe or soil pipe 75
g Horizontally from any building structure or obstruction facing a flue terminal 500
h From any other flue terminal, cowl or combustion air intake 300
j Horizontally from any opening window, door, non-mechanical air inlet or other opening into a building with the
exception of sub-floor ventilation
300
k From a mechanical air inlet including a spa blower. 1000
n Vertically below an opening window, non-mechanical air inlet or any other opening into a building with the
exception of sub-floor ventilation
500
Table 3