D6600/D6100IPv6
UL864 & UL1610 Installation
Supplement
Aug 2012
This document supplements the Conettix D6600/D6100IPv6 Installation and Operation Guide
(P/N: 4998122704-08).
1.0 Network Ethernet Module
In the D6600/D6100IPv6 Installation and Operation Guide (4998122704-08), all references to
Network Ethernet Module are the ITS-D6686-UL and its associated documentation (the Conettix
D6686 Ethernet Network Adapter Installation Guide [F01U269888-01]).
2.0 Additional Printer Specification
In Section 6.0 Printer Specifications of the D6600/D6100IPv6i Installation and Operation Guide
(4998122704-08), include the following specification:
The printer must be installed in the same room as the D6600/D6100IPv6.
3.0 Installation
3.1 All Installations
In Section 7.0 Installation of the D6600/D6100IPv6 Installation and Operation Guide (4998122704-
08), include the following installation requirements and notes:
Install the D6600/D6100IPv6 Communications Receiver/Gateway according to the National
Electrical Code (NFPA 70), the National Fire Alarm Code (NFPA 72), and the local Authority
Having Jurisdiction (AHJ).
UL Standard 827 requires that any central station listed for NFPA 72, Central Station Protective
Signaling, UL Central Station Burglary or Police S
tation Connect Service must have a redundant
receiver on the premises to use if the primary receiver malfunctions.
The D6640
Telephone Line Card
is not intended for new installations, but is suitable for existing or
retrofit sites.
Equipment
between Ethernet Interface Modules and the D6600/D6100IPv6 must be UL Listed
Information Technology Equipment
(ITE).
A “COMM FAIL” message
might indicate a compromise attempt.
To meet requirement UL 1610, Section 63.1: The number of separate signals on a single channel
is
limited to 1000. Exception: There is no limit to the number of signals if the central
-
station equipment
is completely duplicated by standby equipment and a swi
tchover can be accomplished in not more
than
90 sec without loss of signals during this period.
The
D6100IPv6 was tested by UL at 120VAC, 60 Hz.