UL864 & UL1610 Installation Supplement
© Bosch Security Systems, Inc., 2012 Page 2 F01U134241-03
Network Communication - The D6600/D6100IPv6 receiver was evaluated for communication over
Third Party Data Networks for the following services when used with a compatible control unit:
• Standard Line Security for Central Station Burglar Alarm Systems according to UL 1610 and
UL 365
• Phone lines have not been evaluated for line security
• In order to implement the Standard or Encrypted Line Security over the private or public IP
networks, the AES Library must be version TBD. The AES Library was evaluated for 128-bit,
192-bit, and 256-bit encryption.
• Supervision signals between premises alarULm equipment and supervising station alarm
receiver equipment shall be managed by the supervising station receiving equipment and
not an intermediary network agent, device or service.
• To meet UL Standard 827, you must be able to switch from one receiver to a standby
receiver within 30 sec, and then repair the faulty receiver and return it to service within
30 min.
• NFPA 72 requires that if more than eight telephone lines are used, the receiving equipment
must be completely duplicated so that switchover from non-functioning to functioning
equipment can occur within 30 sec (per NFPA 72-2002 8.5.3.2.2.1 Paragraph C).
You must program the parameters described in
Table 1:
Table 1: Parameters to Set
Programming Item Parameter to Set Location in Operation &
Inst. Manual
2.2.21 Buzzer Set to 1 to sound on all events. May be set to 3
when used with an automation system to sound
only when the automation link fails.
Section 10.1.6
Parallel Printer
Set to 1 to print all events. May be set to 3 when
used with an automation system.
2.2.34 Battery
Supervision
Set to 1 to activate. Section 8.0
3.1.2.1 Phone
Supervision
Set to 1 to enable. Section 4.1.3
3.2 Burglar Alarm Applications
For commercial fire and burglary, proprietary and central station application
s that use BIS, the BIS
must be installed on the Listed Bosch model B-010 computer with Bosch model B-008
monitor and SC9002 printer connected.
Install the D6600/D6100IPv6 according to UL Standard 827 for Central Station Burglar Alarm
Systems. Use the D6600/D6100IPv6 in a central station that has backup AC power (according to
UL 827) to supervise certificated accounts.