D7212G Approved Applications Compliance Guide
D7212G
Page 13© 2003 Bosch Security Systems 4998138560C
Current Rating Charts
4.0 Current Rating Charts
4.1 Current Rating Chart for Standby Battery Calculations
ABC
AC Power On
Normal Current (mA)
AC Power Off
Minimum Current
(mA)
In Alarm
Maximum Current
(mA)
Model
Number
Quantity
Used
Each
Unit* Total
Each
Unit Total
Each
Unit Total
D7212G ______ 200 x 1 = 200 200 x 1 = 200 500 x 1 = 500
D125B ______ 20 x Quant. = ____ 19 x Quant. = ____ 123 x Quant. = ____
D127 ______ 13 x
Quant. = ____ 12 x Quant. = ____ 45 x Quant. = ____
D129 ______ 25 x Quant. = ____ 25 x Quant. = ____ 25 x Quant. = ____
D185 ______ 120 x
Quant. = ____ 120 x Quant. = ____ 350 x Quant. = ____
D192C ______ 15 x Quant. = ____ 26 x Quant. = ____ 50 x Quant. = ____
D192G ______ 15 x
Quant. = ____ 26 x Quant. = ____ 50 x Quant. = ____
D1255 ______ 104 x Quant. = ____ 106 x Quant. = ____ 206 x Quant. = ____
D1256 ______ 104 x
Quant. = ____ 106 x Quant. = ____ 206 x Quant. = ____
D1257 ______ 104 x Quant. = ____ 106 x Quant. = ____ 206 x Quant. = ____
D1260 ______ 95 x
Quant. = ____ 97 x Quant. = ____ 200 x Quant. = ____
D720 ______ 55 x Quant. = ____ 20 x Quant. = ____ 75 x Quant. = ____
D8125 ______ 48 x
Quant. = ____ 48 x Quant. = ____ 48 x Quant. = ____
D8125MUX* ______ = ____ = ____
D8127T/U ______ 3 x
Quant. = ____ 3 x Quant. = ____ 4 x Quant. = ____
D8128D ______ 50 x Quant. = ____ 50 x Quant. = ____ 50 x Quant. = ____
D8129 ______ 20 x
Quant. = ____ 20 x Quant. = ____
20 x
Quant. + 25 x
# of relays = ____
D8130 ______ 5 x Quant. = ____ 5 x Quant. = ____ 54 x Quant. = ____
D9127T/U ______ 0.5 x
Quant. = ____ 0.5 x Quant. = ____ 0.8 x Quant. = ____
D9131A ______ 24 x Quant. = ____ 22 x Quant. = ____ 36 x Quant. = ____
Ratings of other devices in the system which are not shown above:
________ ______ ____ x
Quant. = ____ ____ x Quant. = ____ ____ x Quant. = ____
________ ______ ____ x
Quant. = ____ ____ x Quant. = ____ ____ x Quant. = ____
________ ______ ____ x
Quant. = ____ ____ x Quant. = ____ ____ x Quant. = ____
________ ______ ____ x
Quant. = ____ ____ x Quant. = ____ ____ x Quant. = ____
________ ______ ____ x Quant. = ____ ____ x Quant. = ____ ____ x Quant. = ____
Total A = _____ Total B = _____ Total C = _____
* See Table 3 on page 14 for determining maximum currents for the D8125MUX and its accessories.
Table 2: Current Rating Chart for Standby Battery Calculations