D7212GV2 | Operation and Installation Guide | 10.0 Off-Board Relays
42 Bosch Security Systems, Inc. | 5/05 | F01U003805B
10.0 Off-Board Relays
10.1 D8129 OctoRelay
Use the D8129 OctoRelay to add relay outputs to the
system in groups of eight. The D7212GV2 allows up to
24 relay outputs. Review Section 6.0 Power Outputs on
page 24 to ensure that enough power is provided for
the OctoRelays and other powered devices that are
connected to the system.
OctoRelays for relay numbers 1 to 24 connect to
Zonex 1, Terminal 28. Refer to Figure 17 on this page.
Alarm output, auxiliary relay, sensor reset, arming
status, point status, alarm memory, or remote functions
can be assigned to the OctoRelay outputs individually.
Refer to Relay Parameters in the D7212GV2 Program
Entry Guide (P/N: F01U003804) for programming
details.
D8129 Restricted for Fire Systems: D8129 relay
outputs are not supervised and cannot be used in fire
or combined fire and burglary installations for primary
indicating devices.
10.2 Configuring the D8129 OctoRelay
Five switches on the OctoRelay determine the relay
numbers for the eight relay outputs (Table 17).
Table 17: D8129 OctoRelay Switch Settings
Panel Relay
Number
D8129 OctoRelay
Switch Setting
On Panel, Connect
D8129 to:
1 to 8 Off-On-On-On-On Zonex 1 Terminal 28
9 to 16 On-Off-On-On-On Zonex 1 Terminal 28
17 to 24 Off-Off-On-On-On Zonex 1 Terminal 28
Figure 17: D8129 Connections to the D7212GV2
EARTH GRO
COMMON
BATTERY N
Maximum Charging
Current 1.4 Amps.
BATTERY POSITIVE ONLY
RELAY A
RELAY B
RELAY C
+ AUX PO
1
2
3
4
5
6
7
8
9
10
CLASS 2 TRANS
16.5 VAC 40 VAC
Model D1640
Internal ly Fuse
Requires Unsw
Do Not Share
Low Battery
RED
PR
AL
Re
GROUND FAULT DE
En
Di
RED
1
2
3
Pin
Battery
amming
E CONNECTIONS
POWER +
DATA BUS A
DATA BUS B
COMMON
ZONEX OUT 1
ZONEX IN 1
32
31
30
29
28
27
NOT USED
26
25
NOT USED
EX POWER +
24
X COMMON
23
D5200/D5360
PROG CONN
1 2 3 4 567 8
GND
AUX
DATA
1 - D8129 OctoRelays for relay numbers 1 to 24.
Connect OctoRelays in parallel.
2 - Power limited
3 - Supervised, power limited

Table of Contents

Related product manuals