D9412GV2/D7412GV2 | Troubleshooting Guide | 3.0 Troubleshooting
90 Bosch Security Systems, Inc. | 11/05 | F01U011024B
Configuring the Firewall in Windows XP Service Pack
2 for Compatibility with RPS
TTP39: Control Panel Does Not Send
Opening and Closing Reports by
Area
If your PC, with Remote Programming Software (RPS)
installed, runs Windows XP Service Pack 2 and you
use Windows Firewall, you must grant permission to
RPS so that it can conduct network communication
with control panels:
Initial Actions
Ensure that opening and closing reports are enabled in
Gv2MAINPanel Wide ParametersRouting
User Reports.
1. Select StartControl Panel.
Procedure
If the PC’s Control Panel is set to Category
View, select Control PanelSecurity Center.
Under “Manage security settings for:”, click
Windows Firewall. Go to Step 2.
Using RPS or your D5200 Programmer, select
GV2MAINArea Wide Parameters Area Parameters.
Are the areas for which opening and closing reports
are needed set to On?
If the PC’s Control Panel is set to Classic
View, select Control PanelWindows
Firewall. Go to Step 2.
2. Click the Exceptions tab.
3. Click Add Port…
4. In the Name field, enter the name of the port.
Example: RPS_Port
5. In the Port Number field, enter the port number
assigned to your network interface module. For
example, if your network interface module uses
Port 7700, enter: 7700
6. Click UDP.
7. Click OK.
8. Click OK again.
9. Test the connection from within RPS.
Change the settings to On.
Using RPS or your D5200 Programmer, select
GV2MAINArea Wide ParametersOpen/Close
OptionsArea O/C.
Is the Area O/C parameter set to Yes?
Change the Area O/C to Yes.
Using RPS or your D5200 Programmer, select
GV2MAINArea Wide ParametersOpen/Close
OptionsAcct O/C.
Is the Acct O/C parameter set to No?
If Acct O/C is set to Yes, no report is sent until
all areas within the account are armed or
disarmed. The reports are sent only by account,
not by area. Refer to Table 49 on page 91.
Change the Acct O/C parameter to No.
Using RPS or your D5200 Programmer, select
GV2MAINArea Wide ParametersOpen/Close
OptionsRestricted O/C.
Is the Restricted O/C parameter set to No?
If Restricted O/C is set to Yes, the opening and
closing report is not sent until another specified
report is sent. The preferred setting for this
parameter is No. Refer to Table 49 on page 91.
Change Restricted O/C to No.