D9412GV3/D7412GV3 | Operation and Installation Guide | Appendix A: System Wiring Diagrams, Issue A
.
Bosch Security Systems, Inc. | 10/10 | F01U143070-03 67
Figure 36: D9412GV3, Input Points and Peripheral Devices System Wiring
Sw. Aux Pwr
Zone B
Zone A
Pnl Common
Pnl Common
Loop B-
Loop A-
Loop B+
Loop A+
Earth Ground
10
9
5
4
3
8
2
1
7
6
Aux Power
Zone B
Zone A
Common
Loop B-
Loop A-
Loop B+
Loop A+
Earth Ground
10
9
5
4
3
8
2
1
7
6
11
12
13
Loop A+
Loop A-
Loop B+
Loop B-
COMMON
VOLTAGE RANGES
Open 3.7 - 5.0 VDC
Normal 2.0 - 3.0 VDC
Short 0.0 - 1.3 VDC
+
-
TELCO
RING
TIP
PHONE LINE
SEIZED
27
25
EARTH GROUND
COMMON
RELAY A
RELAY B
RELAY C
S4 GROUND FAULT DETECT
Enabled
Disabled
RED
ON when communicating
OFF when idle
ZONEX IN 1
26
ZONEX POWER +
24
ZONEX COMMON
23
PHONE LINE SEIZED LED
TIP
RING
TELCO CORD MODEL D161
ZONEX OUT 2
ZONEX IN 2
PROGRAMMABLE
ALARM OUTPUTS
Terminals
SWITCHED AUX
and
6
7
Terminal
8
Operation Monitor LED
Pulses when Normal
Flickers when Ringing
GREEN
D5200/D5360
PROG CONN
Point 8, S3 Option
Closed = 1 kW EOL
Normal Operation
Open =AB-12 UL
Bell Box 220 kW
25
Point 3
Point 4
161514
Point 1
Point 2
1211 13
Point 5
Point 6
1817 19
Point 7
Point 8
21
20
22
27
BATTERY NEGATIVE ONLY
BATTERY POSITIVE ONLY
+ AUX POWER
CLASS 2 TRANSFORMER
16.5 VAC 40 VA 60 Hz
Model D1640
Internally Fused - Do not short
Requires Unswitched Outlet
Do not share with other equipment
RED
POWER +
YELLOW
DATA BUS A
GREEN
DATA BUS B
BLACK
COMMON
ZONEX OUT 1
N.F.P.A.
Style 4.0
Signaling
Line
Circuits
CAUTION:
Avoid damage to Panel.
Do not connect 24 V to terminals.
Maximum charging current 1.4 A
D9412GV3
1 - (Optional): For 24 V applications use a UL 1481
listed, regulated, power-limited 24 VDC power
supply with a D130 Relay Module. Refer to the
D130 Installation Instructions (P/N: F01U072455)
for correct wiring requirements.
2 - D130 Relay Module
3 - D125B Powered Loop Interface Module
4 - To UL Listed two-wire smoke detectors. Refer to
Two-Wire Smoke Detectors in the
D9412GV3/D7412GV3 Approved Applications
Compliance Guide (P/N: F01U143069) for a
listing of compatible two-wire smoke detectors.
5 - P105BL1 1 kW resistor (P/N: F01U033966):
For typical burglar alarm applications.
6 - D129 Dual Class A Initiation Circuit Module:
Provides optional Waterflow Alarm Retard
feature. Not suitable for two-wire smoke
detectors.
Use zero retard except for waterflow devices.
All external connections except Terminal 5 (battery positive) are power limited.