D9412GV2/D7412GV2
D9412GV2/D7412GV2 Release Notes for Version 7.09
F01U003637-06 Page 12 © 201313 Bosch Security Systems, Inc.
Table
4: Parameters for Heartbeat Poll
Configuration in Version 7.03
1
Number
of IP
Paths
Poll
Rate
(sec)
ACK Wait
Time (sec)
Number of
Retries
1 30 6 2 to 19
1 30 8 2 to 12
1 30 10 2 to 8
1 30 12 2 to 5
1 30 14 2 to 3
1 60 6 2 to 14
1 60 8 2 to 8
1 60 10 2 to 5
1 60 12 2
1
75
2
10
2
3
2
1 90 6 2 to 9
1 90 8 2 to 4
1 90 10 2
1 120 6 2 to 4
1 145 5 2
2
75
2
8
2
3
2
3
75
2
6
2
3
2
4
75
2
5
2
3
2
1
The parameters in this table are for Version 7.03
only
.
2
Recommended settings for the corresponding
number of IP paths.
Corrections allow the
Path # Retry Count
value to be used as the number of retries
instead of the number of transmission
attempts.
When the control panel disconnects from an
RPS session using the network and the
“Reset Panel” checkbox is set, the control
panel now logs a Remote Reset event instead
of a Reboot Event.
Corrections now prevent the D9412GV2 and
D7412GV2 Control Panels from performing a
watchdog reset when an area is armed with
more than 75 manually bypassed points or
has more than 75 force bypassed points.
Corrections now prevent the D9412GV2 and
D7412GV2 Control Panels from performing a
watchdog reset when an area with
A# Area
Type
set to Shared is individually armed.
Shared areas should not be individually
armed or disarmed.
Corrections now prevent a duress passcode
from being accepted by a keypad currently in
an area that has
A# Duress Enable
set to No.
If the Duress feature is used, A
# Duress
Enable
should be set to Yes for all areas.
The alternate function of Area 6 Silent Alarm
Relay parameter was removed. To enable Fire
Trouble Resound support, use
GV2AUXMISCELLANEOUSFire Trouble
Resound.
The alternate function of Area 5 Silent Alarm
Relay parameter was removed. The Ground
Fault detection feature is solely enabled by
closing Switch S4 on the D9412GV2 and
D7412GV2 Control Panels.
Changes now suppress the ALARM SILENCED
message when a user attempts to silence a
Ring Until Restored fire bell. A fire alarm
generated by a point with the Ring Until
Restored (
P# Ring Til Rst
) feature set to Yes
will sustain the fire bell until the sensor is
restored.
Corrections ensure that acknowledged Silent
Alarms scroll correctly on the idle text
displays on the D1260 and D1260B Keypads.
Corrections now allow a user’s token, with
L#
Disarm Level
set to 1, to disarm the interior
of all areas within the scope of the keypad
programmed at
D# CC# Scope
. The keypad
programmed at
D# CC# Scope
must have
CC# Passcode Follows Scope
set to Yes to
disarm the interior of all areas within scope.
Corrections now allow the panel-wide
Communications Failure Relay output to
activate when events in Route Groups 2
through 4 do not reach the central station.
Previously this relay output activated only on
a communication failure for Route Group 1.
2.8 Version 7.02
The Phone Line Supervision feature has
improved accuracy in detecting the phone
line.
The Modem IIIa
2
product ID is changed to the
same ID as the G Series control panels,
allowing compatibility with non-Bosch central
station receivers.
2.9 Version 7.01
The following are corrections and changes made
since Version 6.60 in the G Series Control
Panels.