EasyManua.ls Logo

Bosch EP015 - MAINTENANCE

Bosch EP015
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21
EP Series
8733922168
Revised 12-13 Subject to change without prior notice
Unit Start-Up
IN-WARRANTY MATERIAL RETURN
When contacting your Representative for service
or replacement parts, refer to the model and serial
number of the unit as stamped on the data plate
attached to the unit.
Material may be returned to the factory only with
permission of an authorized factory representative. A
Warranty Return Material” tag must be attached to
the returned material. Assure that all of the
information as called for on the tag is lled out
completely and accurately to expedite handling and
insure prompt issuance of credits.
Freight charges for all items returned to the factory
shall be prepaid. The return of the part does not
constitute an order for a replacement. Therefore, a
purchase order must be entered through your
nearest representative. The order shall include the
part number, model number, and serial number of
the unit involved. If the part is within the warranty
period, and after our inspection of the returned part
proves that the failure is due to faulty material or
workmanship a credit or replacement part will be
issued.
Caution
Parts returned without a completed “Warranty
Return Material” tag will not be credited.
MAINTENANCE
1. Filter changes or cleanings are required at regular
intervals. The time period between lter changes
will depend upon type of environment the
equipment is used in. In a single family home,
that is not under construction, changing or
cleaning the lter every 60 days may be sufcient.
In other applications such as motels, where daily
vacuuming produces a large amount of lint, lter
changes may be need to be as frequent as
biweekly. See unit specications for replacement
lter sizes. Note that horizontal units containing
two lters are taped together at the factory to
facilitate removal. This should be done by end
user as new lters are installed.
Caution
Operating the unit with improper line voltage
or with excessive phase imbalance is hazard-
ous to the unit and constitutes abuse and is
not covered under warranty.
2. An annual “checkup” is recommended by a
licensed refrigeration mechanic. Recording the
performance measurements of volts, amps, and
water temperature differences (both heating and
cooling) is recommended. This data should be
compared to the information on the unit’s data
plate and the data taken at the original startup of
the equipment.
3. The condensate drain should be checked
annually by cleaning and ushing to insure proper
drainage.
4. Periodic lockouts almost always are caused by air
or water ow problems. The lockout (shutdown)
of the unit is a normal protective measure in the
design of the equipment. If continual lockouts
occur call a mechanic immediately and have them
check for: water ow problems, water
temperature problems, air ow problems or air
temperature problems. Use of the pressure and
temperature charts for the unit may be required
to properly determine the cause.

Related product manuals