EasyManuals Logo

Bosch FCP‑320 Series User Manual

Bosch FCP‑320 Series
34 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
16 en | Accessories Conventional Automatic Fire Detectors
2021.03 | 11 | F.01U.004.377
User manual
Bosch Sicherheitssysteme GmbH
5 Accessories
5.1 EOL Module for Line Termination According to EN 54-13
FLM-320-EOL2W EOL-Module
The FLM-320-EOL2W EOL module is a 2-wire module for
terminating a conventional line.
It detects faults in the line and transmits a notification to the
fire panel display.
For a conventional connection one line must not contain
more than 32 automatic detectors.
5.2 Support Plates for Detector Identification
The support plates are made from 1.8mm thick ABS plastic and are clamped between the
detector base and the ceiling.
TP4 400 Support Plate
The TP4400 Support Plate is intended for an installation
height up to 4m and is designed for labels up to a size of
approximately 65x34mm.
15 / 4
TP8 400 Support Plate
The TP8400 Support Plate is intended for an installation
height up to 8m and is designed for labels up to a size of
approximately 97x44mm.
5.3 SK400 Protective Basket
The SK400 Protective Basket is installed over the detector
and gives the detector substantial protection against
damage.
If the detector is mounted in a sports facility, for example,
the protective basket prevents balls or other sports
equipment from hitting the detector and damaging it.

Other manuals for Bosch FCP‑320 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch FCP‑320 Series and is the answer not in the manual?

Bosch FCP‑320 Series Specifications

General IconGeneral
BrandBosch
ModelFCP‑320 Series
CategorySecurity Sensors
LanguageEnglish

Related product manuals