Conventional Automatic Fire Detectors Maintenance and Service | en 25
Bosch Sicherheitssysteme GmbH
User manual
2021.03 | 11 | F.01U.004.377
7 Maintenance and Service
Maintenance and inspection work on security systems are governed in Germany by the
regulations of DIN VDE0833; these regulations stipulate reference to the manufacturer's
instructions for maintenance intervals.
– Maintenance and inspection work should be carried out regularly and by trained
personnel.
– BOSCH ST recommends a functional and visual inspection at least once a year.
Testing Detector Type
FCP-O320
FCP-O320-R470
FCH-T320
FCH-T320-R470
FCH-T320-FSA
FCP-OT320
FCP-OT320-R470
FCP-OC320
FCP-OC320-R470
Check of the LED
display
X X X X
Visual check of the
mounting
X X X X
Visual check for
damage
X X X X
Check the monitoring
range has not been
restricted, for
instance by shelves
or similar
installations.
X X X X
Triggering with hot
air
- X X X
Triggering with Test
Aerosol
X - X X
Triggering with CO
testing gas
- - - X
– FCP-OC320/FCP-OC320-R470
Multisensor detectors with C sensors must be exchanged every 5 years.
An FCP-OC320 and FCP‑OC320‑R470 will deactivate its C sensor after 5years of
operation due to the gas sensor's limited life cycle. The detector continues to function as
an O detector.
Depending on the system, there may be no message to the control panel, and the
deactivation of the C sensor is only noticed when the detector is tested. The FCP‑OC320/
FCP‑OC320‑R470 should therefore be exchanged promptly before 5years of operation
has elapsed.
– Optical smoke detectors should, depending on the environmental conditions, be cleaned
and exchanged regularly.