Conventional Automatic Detectors Installation | en 13
Bosch Sicherheitssysteme GmbH Operation Guide F.01U.002.707 | 8.0 | 2011.10
4.3.2 Wiring the MSR 320
Maximum contact load (resistive load) of the change-over relay:
62.5 VA: 0.5 A at 125 V AC
30 W: 1 A at 30 V DC
NOTICE! The last detector in a conventional line can be terminated either with a terminal
resistor in the detector base or with an FLM-320-EOL2W EOL module. For terminating the line
according to the EN-54-13 standard, the FLM-320-EOL2W EOL module is required.
Legend
ye yellow, connects to b1/b2 + / L..b (conventional)
wh white, connects to a1/a2 - / L..a (conventional)
rd MPA/FAA-420-RI: red, connects to b1
bk MPA/FAA-420-RI: black, connects to c (Indicator output)
gn green, connects to shielding wire
NC / C / NO Changeover relay (for the MSR 320 only)
NO
NC C
c
C
a1/a2
b2
b1
COM
NC NO
wh
bk
rd
gn
ye
ye
max. 3 m
1 A / 30 V DC
0,5 A / 125 V AC
rd
+
bk
MPA/
FAA-420-RI
FLM-420/4-CON
CZM
}
OUT –
FLM-420/4-CON
CZM
}
OUT +