FPP-RNAC-8A-4C | Operation and Installation Guide |
2 Bosch Security Systems, Inc. | 8/09 | F01U025431-02
Notice to Users, Installers, Authorities
Having Jurisdiction, and other involved
parties:
This product incorporates field-
programmable software. In order for the
product to comply with the requirements
in the Standard for Control Units and
Accessories for Fire Alarm Systems,
UL864, certain programming features or
options must be limited to specific values
or not used at all as indicated below.
Program Feature or Option Permitted in UL864?
(Y/N)
Possible Settings Settings Permitted in
UL864
Ground Fault Detection
disable
N Jumper in place (enabled)
Jumper removed (disabled)
Jumper in place (enabled),
only