EasyManua.ls Logo

Bosch Integra 500 - Page 11

Bosch Integra 500
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 720 680 226
Installation instructions
11
3.3.2 Vent specifications
Establish vent clearances that comply with the vent
manufacturer's specifications and all applicable
national/local codes.
Venting specifications
Condensate drain requirements
An external condensate drain (not supplied with the
heater) must be installed under the following
conditions:
All vertical terminating vent installations.
Horizontal terminating vent installations where the
total linear vent length is greater than 6 feet (1.8 m).
Vent installations where any section of the exhaust
vent pipe passes through an unconditioned space.
Minimum combustion air and exhaust pipe
length
The minimum exhaust pipe length is 3 feet (1m) of
straight vent pipe. The minimum combustion air pipe
length is one 90° elbow.
Maximum combustion air and exhaust pipe
length
The following tables (Tables 5 & 6) display the
maximum allowable straight pipe lengths for
combustion air and exhaust piping with consideration to
the number of elbows used.
Step 1: If using the twin pipe penetration system, refer
to table 5. If using the concentric vent kit
system, refer to table 6.
Step 2: Total the number of 90° elbows and 45°
elbows used on the exhaust piping.
Step 3: Use this value in the appropriate table to
determine the maximum straight exhaust pipe
length allowed.
Step 4: Total the number of 90° elbows and 45°
elbows used on the combustion air piping.
Step 5: Use this value in the appropriate table to
determine the maximum straight combustion
air pipe length allowed.
* Not allowed. At least one 90º elbow required.
** Not allowed. Minimum of 3 feet (1m) of straight pipe required.
* Not allowed. At least one 90º elbow required.
** Not allowed. Minimum of 3 feet (1m) of straight pipe required.
Note: Include pipe length that is part of the concentric terminal.
Diam. Aproved terminals
E
x
h
a
u
s
t
3 or 4 inches
“T” terminal
90° elbow
Concentric
(196016)
I
n
t
a
k
e
3 or 4 inches
“T” terminal
90° elbow
Concentric
(196016)
Table 4 Venting specifications for intake and exhaust
i
Note: 90° elbows used for
terminations should not be counted
in the exhaust and combustion air
piping.
Twin Pipe
System
# of 90° elbows
0 1 2 3 4
# of 45°
elbows
0 N/A* 26 21 16 11
1 N/A* 23 18 13 8
2 23 20 15 10 5
3 20 17 12 7 N/A**
4 17 14 9 4 N/A**
5 14 11 6 N/A** N/A**
6 11 8 3 N/A** N/A**
Maximum allowable straight pipe length (ft)
Table 5 Maximum allowable straight pipe length (twin
pipe)
Concentric
pipe System
# of 90° elbows
0 1 2 3 4
# of 45°
elbows
0 N/A* 18 13 8 3
1 N/A* 15 10 5 N/A**
2 15 12 7 N/A** N/A**
3 12 9 4 N/A** N/A**
4 9 6 N/A** N/A** N/A**
5 6 3 N/A** N/A** N/A**
6 3 N/A** N/A** N/A** N/A**
Maximum allowable straight pipe length (ft)
Table 6 Maximum straight pipe length (concentric ter-
minal)

Related product manuals