RE 30277-02-B/07.2016, HEDE 10-3X, Bosch Rexroth AG
P = system pressure
UMRL = Upper measuring range limit
Current output:
Within the measuring range of the device the output signal ranges
between 4 and 20 mA.
Moreover, the following is signaled:
System pressure above measuring range: 20...20.5 mA
Error signaling from 21.5 mA on.
System pressure below measuring range: 4...3.8 mA
Voltage output:
Within the measuring range of the device the output signal ranges
between 0 and 10 V.
Moreover, the following is signaled:
System pressure above measuring range: 10...10.3 V
Error signaling from 11 V on.
5.2.3 IO-Link
General information
The pressure sensor is provided with an IO-Link communication
interface, which requires an IO-Link-capable module (IO-Link master)
for operation.
The IO-Link interface enables direct access to the process and
diagnostic data and provides the possibility of setting parameters of
the pressure sensor during operation.
In addition, communication is possible via a point-to-point connection
with a USB adapter cable.
You can nd the IODDs necessary for the conguration of the device,
detailed information about process data structure, diagnostic
information and parameter addresses as well as the required
information on the necessary IO-Link hardware and software at
www.boschrexroth.de/hede10-3x