RE 30232-01-B, Edition 04.2020, Bosch Rexroth AG
Installation | Valve amplifier VT-MSPA2-2X 17 | 36
Table 8: Clamping range, rated connection
Min. Max.
Rigid 0.2 mm² 2.5 mm²
Flexible 0.2 mm² 2.5 mm²
Flexible with wire end ferrule 0.25 mm² 2.5 mm²
The length to be stripped is 10 mm each.
7.5.3 Connecting the individual contacts
Fig. 3: XG20/XG21: “PUSH-IN“ contact
7.5.4 Suppressing interference of the system
Should interference occur in conjunction with signals of the VT-MSPA2-2X, check
the interference suppression of other electrical components, e.g. as follows:
Table 9: Suppressing interference
Possible causes of faults
Switched inductance DC: antiparallel free-wheeling diode over actuator winding
AC: type-related R/C combination over actuator winding.
Electric motors R/C combination from each motor winding to earth.
Frequency converter Inlet filter in the voltage supply of the frequency converter
Motor control lines shielded and installed separately from other
cables and/or output filter for motor cables.
Large-area contact of the frequency converter housing to the
rear wall of the control cabinet